Limit switch box with adjustable stainless steel mounting bracket. Up to 4 switches possible. ATEX-execution.

  • SIL
  • ATEX

Data sheet TRI-SWITCHBOX WAVE ATEX Operating manualDeclaration of conformity CE


Offer request  Contact us

TRI-SWITCHBOX WAVE ATEX

Limit switch box with adjustable stainless steel mounting bracket. Up to 4 switches possible. ATEX-execution.

  • SIL
  • ATEX

Data sheet TRI-SWITCHBOX WAVE ATEX Operating manualDeclaration of conformity CE


Offer request  Contact us

Technical data

Body:

Conductive vestamid

Cover:

Conductive vestamid

Protection:

IP 66 according to DIN EN 60529
and DIN EN 60079-0

Temperature range:

Ex ia: -25°C to +70°C
Ex e / Ex t: -20°C to +40°C

Cable gland:

M20x1.5 black or blue

 

Adjustable stainless steel mounting bracket

Easy mounting on actuators with a 
hole spacing of 80x30mm and 130x30mm and a 
shaft height of 20,30,40, and 50mm

On Request:
- Switch box with plug connection
- Body made of aluminium (-40°C to +60°C)
- Low temperature version (-55°C)
- Other inductive contacts
- Magnetic valve connector with cable

TRI-SWITCHBOX WAVE ATEX

Mechanical Switches

No. TRI-MATIC

Code

Technical Data Switch *

1715793

EVE2M01-ED 2SPDT BARTEC 07-1511-1530

A - 1

Proximity Sensors

1716329

EVE2I01-IA 2x IND. P+F NJ2-V3-N "NC"

A - 2

1716330

EVE2S01-IA 2x IND. P+F SJ3,5-N "NC"

A - 3

1716331

EVE2I01-356-K3 2x P+F NBB2-V3-E2-3G

A - 4

Technical Data Switch

 

A - 1

 

A - 2

A - 3

 

A - 4

Producer switch

Bartec

Producer switch

P+F

P+F

Producer switch

P+F

Switch type

07-1511-1530

Switch type

NJ2-V3-N

(N.C.)

SJ3,5-N

(N.C.)

Switch type

NBB2-V3-E2-3G-3D

(PNP N.O.)

Function

3-wire N.O. / N.C.

Voltage

8.2V DC

8V DC

Voltage

10-30V DC

Maximum current

DC 150mA / AC 4A

Maximum current

≤ 1 mA

≥ 3mA

≤ 1 mA

≥ 3mA

Maximum current

100mA

Voltage

24V DC / 250V AC

Frequency

1000Hz

3000Hz

Frequency

1000Hz

Contacts

Silver

SIL Level

SIL 1-3 (IEC 61508:2010)

SIL 1-3 (IEC 61508:2010)

SIL Level

---

Ambient temperature

Vestamid: -20°C…+40°C

Aluminium: (-55°C)              

 -20°C…+60°C

Ambient temperature

-25°C…+70°C

-25°C…+70°C

Ambient temperature

Vestamid: -25°C…+40°C

Aluminium: -25°C…+60°C

ATEX

Ex II 2G Ex db eb IIC T6 Gb

Ex II 2D Ex t IIIC T80°C Db

ATEX

Ex II 2G Ex ia IIC T6 Gb

Ex II 2D Ex ia IIIC T80°C Db

Ex II 2G Ex ia IIC T6 Gb

Ex II 2D Ex ia IIIC T80°C Db

ATEX

Ex II 3G Ex nA IIC T6 Gc

Declaration of conformity CE

CE Type examination certificate

IBExU 12 ATEX 1022 X

CE Type examination certificate

IBExU 11 ATEX 1154

IECEx IBE 13.0042

IBExU 11 ATEX 1154

IECEx IBE 13.0042

 

Ex II 2D/3D Ex t IIIC T80°C Dc

IBEXU 12 ATEX 1022 X

IECEX IBE 13.0041 X

Ex zone

Zone 1, 21

Ex zone

Zone 1, 21

Zone 1, 21

Ex zone

Zone 2, 21 + 22

Other categories

Quality that's got it all